Dynamic Pass Box is designed to allow material transfer through controlled environment without much personal movement.Furthermore, this box helps in prevention of contaminants enterance either in clean room or between various classified areas. Dynamic Pass Box that we deliver in the market is available at most economical prices.
Material Of Construction :
Standard Features:
- Minipleat HEPA Filter EU-14 Grade, efficiency 99.999% down to 0.3µ.
- Pre filters EU 6 Grade with average efficiency of 60-80% down to 5µ.
- Fresh Air Filter EU 6 Grade with efficiency of 60-80% down to 5 u
- AC Centrifugal Motor Blower with Regulator for speed controlling.
- Magnehelic Differential Pressure Gauge.
- SS 304 double walled insulated doors with toughened glass with SS 304
Handles & Hinges.
- SS304 Perforated grills on side walls for return air.
- Electro-Magnetic Interlocking card with LED display controlling on either
side of the door to ensure that only one side door can be opened at a time.
Manual On-Off Switches for Blower, LED & U.V Light.
- 6/16 Amp single-phase switch socket.
- U. V. Light providing 256nm wavelength with Hour Meter.
Led Light with SS covering.
- PAO Test port for HEPA filter integrity test.
- Pass box support stand with Nylon levelling pad In Back side for wall
mounted pass box
- Drop Seal in doors, base sheet or SS angle (which is to be grouted in floor)
in bottom for floor mounted pass box.
- SS304 access panel on front & back side for service & maintenance.
- S$ 304 ball catcher for holding the door during power failure.
- SS304 channels to cover HEPA clamps.
Standard Dimensions :
Internal Dimension (mm)
|
Model |
Width |
Depth |
Height |
Wall Mounted |
450 |
450 |
450 |
600 |
600 |
600 |
Floor Mounted |
900 |
900 |
900 |
1200 |
1200 |
1200 |
1500 |
1500 |
1500 |
Options & Accessories :
- S$ 304 protective grill below Hepa filter.
- Audio / Visual alarm for blower tripping with Fault
Acknowledgement & Reset Switch.
- Digihelic/Photohelic Gauge with High / Low Indicators.
- Adjustable Timer to set operation time.
- Flame Proof Execution as Explosion proof electrics for
Flameproof applications.
Performance :
- Air cleanliness : ISO Class 5 (ISO 14644-1:1999 (E) /
Class 100.
- Air Velocities : 0.45 + 0.05 mps@ 6 Inch below Hepa
Terminal.
- Air Flow : Vertical - Recirculatory.
- Noise Level : Less than 67 db on Scale 'A'.
- Vibration level : Minimum.
Power Supply :
- 230 VAC 1θ, 50-60HZ & for FLP 415 VAC, 3θ, 50-60Hz.